Google Cloud's London Outage: What EMIs and PIs Should Fix
Dmytro Medvid, Founder · · 13 min read

Key takeaways
- On 20 October 2026 a power failure in Google Cloud's europe-west2-b zone disrupted services across the London region for about six hours, because failover traffic saturated the surviving zones and regional control planes depended on the failed zone.
- The Bank of England, PRA and FCA learned of the disruption at 09:09 BST from affected firms, not from Google, and say the critical third parties regime does not replace firms' own responsibility for operational resilience.
- UK EMIs and PIs must stay within impact tolerances under SYSC 15A and report major incidents to the FCA within 4 hours; that 4-hour rule continues under the new PS26/2 regime from 18 March 2027.
- Under DORA an outage that affects more than 10% of a service's clients and causes more than 2 hours of downtime on a critical service is a major ICT incident, with an initial notification due within 4 hours of classification and normally no later than 24 hours after awareness.
- For the payment-critical path — ledger, payments, card authorisation and login — EMIs should test a regional failure, check their suppliers' hosting regions and measure recovery to the end of reconciliation, not to the provider's 'resolved' time.
On 20 October 2026 one zone of Google Cloud's London region lost power, and for most of a working morning banks, payment firms and their suppliers in the UK struggled to serve customers. The lesson for e-money and payment institutions is specific: a single-zone failure spread across the whole region, the regulators learned about it from firms rather than from Google, and responsibility for operational resilience stayed with the regulated firm. If your app, ledger, card authorisation or KYC vendor runs in one region, 20 October is the test scenario your board should be asking about.
This article reconstructs what happened from Google's own incident report and the authorities' letter to Parliament, explains why multi-zone set-ups did not fully protect people, and sets out what UK and EU rules expect from an EMI or PI when this happens again — including whether an outage like this is a reportable "major" incident.
What happened on 20 October
Google's final incident report, posted on 4 November, gives the sequence. The data centre hosting zone europe-west2-b had been placed on a single utility feed so that its second feed could be repaired, after issues were found during a quarterly generator load test on 14 October. At 06:53 BST an underground cable fault took out the remaining feed. The UPS batteries carried the load for about five minutes as designed, but the generators never started: the controller that should have ordered them to start read live voltage on the disconnected feed and concluded that mains power was still available.
From there the timeline (all BST) runs:
- 07:00 — servers, storage and network hardware in zone b lose power.
- 07:04 — Google's monitoring alerts its engineers.
- 07:09 — automated failover moves traffic towards zones a and c.
- 08:20 — power is back in the data halls; storage then needs a long, careful recovery after the unclean shutdown.
- 12:11 — Google Cloud services and APIs are fully available again, though some virtual machines are not.
- 13:08 — 99.5% of Compute Engine VMs are healthy; Google treats this as recovery for most customers.
- 15:03 — the incident is closed after a tail of isolated workloads recovers.
Some services took longer. Google reports that its managed Kubernetes service was disrupted for 7 hours 34 minutes, and that a small number of Cloud SQL instances only recovered at 19:00. Restoring the platform is also not the same as restoring your service: the Bank of England and FCA note that "some firms required additional time to restore their own services". Reuters reported that, according to Revolut's website, logins, card payments and cash withdrawals were affected at Revolut, and The Register lists Lloyds, HSBC and Royal Mail among the organisations hit.
Why multi-zone was not enough
Cloud regions are split into zones so that losing one zone should not matter to well-built applications. Google's report says this did not fully hold. Resources that lived only in zone b were unavailable "within the design of a zonally-scoped system" — that part is expected. But "some customers running workloads in unimpacted zones (europe-west2-a and europe-west2-c) or across regional architectures also experienced unexpected impact". Google gives two causes:
- Demand surges on the surviving zones. When everything failed over at once, redirected database failovers, queries and compute workloads "saturated available compute slots and processing capacity" in zones a and c. Kubernetes clusters tried to scale up in the surviving zones, and those scale-ups "were impacted by available capacity".
- Control-plane dependencies across zones. Regional services made calls to metadata and catalogue components sitting in the dead zone, and those calls timed out. Customers could not reliably create, update or delete some regional resources. Google calls this "not a full regional control-plane outage, but certainly a degraded state".
Put simply, your redundancy plan assumed spare capacity and a working control plane in the same region, and on the day neither was guaranteed. That matters for EMIs because the failover moment is exactly when a payments stack needs to spin up capacity — to drain queued payments, reconcile, and absorb customers retrying.
How one zone's power cut became a regional problem
- The site was already on one utility feed while the second was being repaired. When that feed failed, the generator controller misread the situation and never started the generators.
- Workloads failed over to zones a and c within minutes. The sudden demand saturated their capacity and slowed autoscaling.
- Regional control planes still called components in the dead zone. Those calls timed out, so even multi-zone services degraded.
- Firms were hit directly and through unregulated suppliers running in the same region.
- The authorities learned of the disruption at 09:09 from affected firms, not from Google. Responsibility for the service stayed with the firms.
Simplified from Google's incident report of 4 November 2026 and the Bank of England/FCA letter of the same date. Times BST.
What the regulators have said so far
The joint letter of 4 November from Andrew Bailey and Nikhil Rathi to the Treasury Committee is an initial response; a fuller one is promised by 20 January 2027 after a post-incident review. Four points in it matter to an EMI or PI.
Google is now a designated critical third party, but that changes nothing about your duties. HM Treasury designated Google Cloud EMEA Limited as a critical third party on 13 July 2026, alongside Microsoft, Amazon Web Services and Oracle entities. The letter says the regime "complements, rather than replaces, the responsibilities of regulated firms", which "remain responsible for their own operational resilience and for managing the risks arising from their reliance on third parties". The same applies in the EU: Google Cloud EMEA Limited is one of the 19 providers on the ESAs' list of critical ICT third-party providers under DORA, and the EBA told Reuters it had contacted Google to assess the impact on EU financial entities. Oversight of the provider sits alongside your obligations; it does not absorb them.
The authorities heard about it from firms. "We became aware of the disruption at 09:09 BST through affected firms, not initially through a notification from Google itself." That was more than two hours after the zone lost power, and the first signal came from affected firms. The post-incident review will assess how effectively Google and affected firms limited the impact and restored services, so expect questions about your own response.
The expectation on assurance is explicit. The authorities say firms should obtain "sufficient assurance that their material third parties can respond to and recover from severe disruption", and where that assurance cannot be obtained "firms should strengthen their own contingency arrangements and consider practicable alternative provision". That sentence is the standard your board will be measured against.
Supply chains spread the impact. The outage "also affected unregulated third-party service providers that provide outsourced services to regulated firms, creating indirect effects through firms' supply chains." An EMI can run its own stack across two regions and still go down because its card processor, KYC provider or core platform vendor did not.
The authorities say some consumers suffered material disruption while firms could not provide services, but they have identified no material ongoing effects on consumers and no implications for market integrity or wider financial stability. That is a statement about the system, not about any single firm's compliance.
Your obligations as a UK EMI or PI
The FCA's operational resilience rules in SYSC 15A apply to authorised and registered EMIs and payment institutions, for their payment services and e-money business (FCA). Since 31 March 2025 you must be able to stay within your impact tolerance for each important business service in a severe but plausible disruption. The FCA's one-year review reminds firms that they must assess their ability to remain within impact tolerance annually, and cites using real-world incidents to calibrate tolerances as good practice.
Three practical consequences after 20 October:
- Re-test the scenario you thought was covered. If your severe-but-plausible scenarios included "loss of a cloud zone" and your answer was "multi-zone deployment", 20 October shows the assumption needs evidence. Run the test with surviving zones under load and the regional control plane degraded, not just with one zone switched off.
- Check your impact tolerance against the clock. Platform recovery for most customers took about six hours, and some managed services took longer; then your own restart, reconciliation and payment backlog come on top. If your tolerance for "make a payment" is shorter than that, you either need a recovery path that does not wait for the region, or a reasoned change to the tolerance.
- Incident reporting is already tight for payments firms. Under regulation 99 of the Payment Services Regulations 2017, PSPs must notify the FCA of major operational or security incidents, with an initial report due within 4 hours (SUP 15.14). From 18 March 2027 the FCA's new single regime in PS26/2 takes over. Most firms get a guidance expectation of an initial report within 24 hours of determining a threshold is met, but PSPs keep a hard 4-hour deadline "of first detecting a major operational or security incident" (new SUP 15.14.18DD), followed by intermediate updates and a final report within 30 working days of resolution (60 at most). PS26/2 also brings notifications of material third-party arrangements for authorised EMIs and PIs, which we covered in our outsourcing and vendor rules guide.
Your obligations as an EU EMI or PI under DORA
DORA covers payment institutions, account information service providers and e-money institutions, including exempted (small) PIs and EMIs, which get the simplified ICT risk management framework of Article 16 instead of Articles 5 to 15 (Regulation (EU) 2022/2554). For a fully authorised firm, the most relevant provisions are:
- Article 11 — an ICT business continuity policy with response and recovery plans for critical or important functions.
- Article 12(4) — firms other than microenterprises "shall maintain redundant ICT capacities equipped with resources, capabilities and functions that are adequate to ensure business needs". Microenterprises must assess whether they need them.
- Article 12(6) — recovery time and recovery point objectives per function, which "in extreme scenarios" must still meet agreed service levels.
- Articles 18 and 19 — classify ICT-related incidents and report major ones to your competent authority.
Was it a "major" ICT incident?
Under Delegated Regulation (EU) 2024/1772, an incident is major if it affected critical services and either involved successful, malicious and unauthorised access that may result in data losses, or met at least two of the other materiality thresholds. The ones an outage like this tends to hit are:
- Clients, counterparts and transactions — more than 10% of clients using the affected service, or more than 100,000 clients, or more than 10% of the daily average number or value of transactions for that service (more than 30% of financial counterparts, or any affected client or counterpart you have identified as relevant, also counts).
- Duration and service downtime — the incident lasts more than 24 hours, or service downtime exceeds 2 hours for ICT services supporting critical or important functions.
- Geographical spread — impact in two or more Member States.
- Economic impact — costs and losses above €100,000.
- Reputational impact and data losses — for example media coverage or repeated complaints, or an impact on the availability, authenticity, integrity or confidentiality of data that affects your business objectives or regulatory compliance.
An EMI whose card and payment services were down for five hours or more for most of its customers would typically meet two thresholds, clients and downtime, and so would likely have a major incident, whatever caused it. The reporting deadlines in Delegated Regulation (EU) 2025/301, Article 5, are: initial notification within 4 hours of classifying the incident as major and no later than 24 hours after becoming aware of it; an intermediate report within 72 hours of the initial notification; a final report no later than one month after the latest intermediate report. If a deadline falls on a weekend or bank holiday in your Member State, you may file by noon on the next working day. For the initial notification and intermediate report this relief does not apply to entities identified as essential or important under NIS2, or to significant or systemic firms whose competent authority has removed it.
Use the calculator below to run your own incident through the test. It applies Articles 8 and 9 of the Delegated Regulation in simplified form (it leaves out the financial-counterparts and 'relevant clients' tests); it does not replace your incident manager's assessment.
Was it a major ICT incident under DORA?
- Other materiality thresholds met (of 6)
- 2
- Major incident? (1 = yes, 0 = no)
- 1
The initial notification is due within 4 hours of classifying the incident as major and no later than 24 hours after becoming aware of it; if you only classify it as major after those 24 hours, you have 4 hours from classification. Recurring smaller incidents can also add up to a major one. UK PSPs: separate FCA 4-hour rule.
Applies Articles 8 and 9 of Delegated Regulation (EU) 2024/1772 in simplified form. Defaults: an EMI whose payments were down for 5.5 hours for 60% of its customers. Not legal advice.
Single zone, multi-zone, multi-region: what each would have meant
Neither the FCA nor DORA prescribes an architecture. Both expect you to plan and test for severe disruption to your critical services. Here is how the main deployment patterns would have fared on 20 October, based on Google's account. It is our assessment, not a regulatory standard.
Deployment patterns against the 20 October scenario
| Criteria | ||||
|---|---|---|---|---|
| Outcome on 20 October | Down until zone b recovered (about 5.5 hours or more) | Mostly up, but some saw errors, slow failover and blocked scaling | Could serve from another region if data and capacity were ready | Not exposed to this event for the functions moved |
| Hidden dependency exposed | Everything sits in one building | Spare capacity and the regional control plane | Data replication lag, DNS and identity services | Data sync and two sets of operational skills |
| Typical relative cost | Lowest | Moderate | Higher: duplicate capacity and replication | Highest: two platforms to run and test |
| Survives loss of one zone | No | Yes | Yes | Yes |
| Survives regional degradationOnly if failover is tested under load | No | No | Yes | Yes |
| Reasonable fit | Internal tools, non-critical batch jobs | Baseline for any payment service | Ledger, card authorisation, payments, customer login | Large firms, or a narrow fallback such as card authorisation |
For an EMI's payment-critical path, multi-zone is the minimum, not the full answer. Plan for a regional failure, then decide which functions justify the cost.
Our reading of Google's incident report. Costs are relative and depend heavily on design.
Four points from the incident report:
- Capacity is not guaranteed at failover time. Google's engineers "adjusted scheduler allocations and capacity limits... to prioritize active customer reservations". If your recovery plan relies on autoscaling into a neighbouring zone, ask your cloud team whether you hold reserved capacity there, and whether that is worth paying for on the payment-critical path.
- Managed databases can be slower to fail over than you think. Highly available Cloud SQL instances failed over immediately unless their regional persistent disks were affected; most of the rest recovered around 09:00 and a few only by 19:00. Know which of your databases is which, and what your recovery point objective for the ledger actually is.
- Your recovery does not end when the provider's does. After the platform is back, you still have to restart services, clear queued payment messages, reconcile balances against your banking partners and answer customers. Measure your impact tolerance against the end of that work, not against the provider's "resolved" time.
- Card authorisation needs a plan of its own. If your issuer processor or your own authorisation service runs in the affected region, card payments fail at the point of sale. Check whether your processor offers stand-in processing, what limits apply, and how stand-in decisions are posted back to your ledger afterwards. Our article on BIN sponsorship and card issuing explains who sits in that chain.
Look at your vendors' regions, not just your own
The authorities' point about unregulated suppliers needs its own review. An EMI's critical path typically includes a core banking or ledger platform, a card processor, KYC and sanctions screening, transaction monitoring, a customer-messaging service and the banking partner's API. Each may run on a hyperscaler, and several may share a region.
Ask each material supplier four questions: which cloud provider and region host the services you use; whether they fail over to another region and how often they test it; what happened to their service on 20 October, with times; and how and when they will notify you of an incident. DORA's register of information already expects you to record these dependencies, and in the UK your SYSC 15A mapping and outsourcing rules do too, with PS26/2's material third-party register and notifications following from 18 March 2027; 20 October gives you a concrete reason to ask now. If several critical suppliers share one region, that is a concentration risk worth putting in front of your board, even if each contract looks fine on its own. Our banking partner exit plan applies the same logic to bank relationships.
Post-20 October resilience review for EMIs and PIs
- List every important business service or critical function and the cloud regions it depends on
Include your own hosting and each supplier on the critical path.
- Ask material suppliers for their hosting region, failover design and 20 October timeline
Record answers in your DORA register of information or FCA third-party records.
- Re-run the 'loss of a zone' scenario with degraded neighbouring zones
Assume scaling is slow and regional APIs return errors.
- Add a 'loss of a region' scenario for the payment-critical path
Ledger, payments, card authorisation, customer login, safeguarding reconciliation.
- Compare impact tolerances and RTOs with a six-hour provider outage plus your own recovery
Include backlog processing and reconciliation time.
- Confirm recovery point objectives for the ledger and payment queues
Know which databases fail over automatically and which need manual work.
- Check card stand-in processing with your processor
Limits, risk rules and how stand-in approvals post to the ledger.
- Rehearse incident classification and the regulator clock
UK PSPs: 4 hours from detection. DORA: 4 hours from classification, 24 hours from awareness at the latest.
- Prepare customer messages and status page wording in advance
SYSC 15A requires an internal and external communication strategy.
- Document the lessons learned and the remediation owner
Both regimes expect post-incident reviews to change something.
A working list for the next board or risk committee. Progress is saved on this device.
What this means if you are building or buying a platform
For firms still choosing their core stack, 20 October is a useful due-diligence script. Whether you build in-house or buy a white-label platform, the questions are the same: where does the ledger run, what is the tested recovery time for the payment-critical path, and what evidence will the vendor give you for your own operational resilience self-assessment. A vendor that cannot answer with dates and test results is asking you to carry that risk blind. The technology checklist for launching an EMI covers the rest of the stack.
This article explains published rules and regulators' statements; it is not legal advice. Check incident classification and reporting decisions with your compliance team, counsel or competent authority.
Our view
The 20 October outage had ordinary causes. A cable fault, a maintenance posture and a misconfigured controller are the usual ingredients of real incidents, and the cascade that followed, with failover traffic swamping the surviving zones, is exactly what resilience testing is supposed to find. Designation of the hyperscalers as critical third parties in the UK and EU is meant to improve oversight of the providers, but both the authorities' letter and DORA leave responsibility for operational resilience with the regulated firm.
For an EMI or PI, the proportionate response is not to move everything to two clouds. It is to treat "the region is degraded" as a real scenario for the small set of functions that customers cannot live without — balances and ledger, payments, card authorisation and login — and to prove, with a test, how long recovery takes. Then do the same for the suppliers on that path. For many firms the expensive part will not be the second region but the reconciliation and operational work that nobody has rehearsed.
If you are rethinking how your ledger, back office and integrations should be structured to make that work easier, our platform gives you a double-entry ledger with an audit trail of every posting, and our custom development team can help design the reconciliation and integration work around it. Tell us what you're building.
FAQ
What caused the Google Cloud London outage on 20 October 2026?
An underground cable fault cut the last utility feed to the data centre hosting zone europe-west2-b, which was already on a single feed while its second feed was under repair. A misconfigured generator controller read voltage on the disconnected feed and never started the generators, so the UPS batteries ran out and the zone lost power at 07:00 BST.
Why were multi-zone applications affected too?
Google says two things spread the impact beyond the failed zone: the sudden failover demand saturated compute capacity in zones a and c, and regional control planes made calls to components in the offline zone that timed out. Some customers in unaffected zones or regional architectures saw errors, slow failover and blocked scaling.
Does Google's critical third party designation reduce an EMI's own obligations?
No. The Bank of England and FCA say the critical third parties regime complements firms' responsibilities, and firms remain responsible for their own operational resilience and third-party risk. DORA's oversight of critical ICT providers in the EU works the same way.
Does a six-hour cloud outage have to be reported?
Often yes. UK payment service providers must report major operational or security incidents to the FCA within 4 hours of detection. Under DORA, an outage that affects a critical service and meets two materiality thresholds, such as more than 10% of clients and more than 2 hours of downtime, is a major incident with an initial notification due within 4 hours of classification.
Should an EMI move to multi-region or a second cloud provider?
Neither rulebook prescribes an architecture. A proportionate approach is multi-zone as a floor for every payment service, and a tested regional failover for the few functions customers cannot do without, such as the ledger, payments, card authorisation and login. A second provider usually makes sense only for large firms or a narrow fallback.
Sources
- Google Cloud Service Health: incident report, europe-west2, 20 October 2026 (posted 4 November 2026)
- Bank of England, PRA and FCA letter to the Treasury Committee on Critical Third Parties regime and Google Cloud service disruptions, 4 November 2026
- Reuters: Europe's financial regulators query Google over cloud outage that hit banks, 21 October 2026
- The Register: When datacenters lose power, generators should kick in. That didn't happen for Google in London, 5 November 2026
- European Supervisory Authorities designate critical ICT third-party providers under DORA, 18 November 2025
- FCA: Operational resilience
- FCA: Operational resilience insights and observations one year on
- FCA PS26/2: Operational incident and third party reporting
- Regulation (EU) 2022/2554 on digital operational resilience (DORA)
- Commission Delegated Regulation (EU) 2024/1772 on classification of ICT-related incidents
- Commission Delegated Regulation (EU) 2025/301 on incident notification content and time limits